Variable Shunt Reactors for outdoor installation for SLF02

Delivery of four (4) variable Shunt Reactor for outdoor installation at substation Idom-lund: Rated voltage Ur: 235 kV Power rating: 60-120 Mvar Regulation Range: 50 % or above Type of regulation: onload (OLTC) Cooling: ONAN Maximum sound power level: 80 dB(A), preferably lower, (at max. operating voltage 245 kV) Corrosion Protection: C5VH or above Max. operating voltage Umax: 245 kV Frequency: 50 Hz Short circuit level 40kA Magnetic characteristic: The core must be linear up to 1.5 times rated voltage.

Buyer

Energinet Eltransmission A/S

Value

€19,802,724

Published

10 Aug 2026

Closes

Not provided

Procurement details

Source

TED (EU)

Region

Denmark

Procurement method

Selective

Category

Goods

Contract starts

8 Jun 2026

Contract ends

31 Jan 2031

CPV classifications

31170000

Transformers

31000000

Electrical machinery, apparatus, equipment and consumables; lighting

Lots

Lot LOT-0000 Variable Shunt Reactors for outdoor installation for SLF02

€19,802,724

Delivery of four (4) variable Shunt Reactor for outdoor installation at substation Idom-lund: Rated voltage Ur: 235 kV Power rating: 60-120 Mvar Regulation Range: 50 % or above Type of regulation: onload (OLTC) Cooling: ONAN Maximum sound power level: 80 dB(A), preferably lower, (at max. operating voltage 245 kV) Corrosion Protection: C5VH or above Max. oper...