Main LV to sub main feed cable replacement
The existing cables are over 20 years old and have been subject to degradation due temperature variations through power loading and the local environment, currently the feed cable to FCS sub main panel failed an insulation resistance test with a reading of 800K Ohms, this reading fluctuates between 800k Ohms and 1.2 M Ohms . The pass level is 1 M-Ohm, we are experiencing these readings on testing other main feed cables (chilled water feed cables) (north main feed cable) (BSD main and HVac feed cables) so a programm...
Buyer
Medicines and Healthcare Products Regulatory Agency
Value
£549,087
Published
18 Nov 2016
Closes
20 May 2016
Procurement details
Source
Contracts Finder
Region
East of England
Procurement method
Not Specified
Category
Works
Contract starts
Not provided
Contract ends
Not provided
CPV classifications
44322000
Cable accessories
Lots
Lot default Main LV to sub main feed cable replacement
£549,087
The existing cables are over 20 years old and have been subject to degradation due temperature variations through power loading and the local environment, currently the feed cable to FCS sub main panel failed an insulation resistance test with a reading of 800K Ohms, this reading fluctuates between 800k Ohms and 1.2 M Ohms . The pass level is 1 M-Ohm, we are...
Delivery: East of England · United Kingdom, East of England, United Kingdom