Main LV to Sub Main Feed Cable Replacement
The existing cables are over 20 years old and have been subject to degradation due temperature variations through power loading and the local environment, currently the feed cable to FCS sub main panel failed an insulation resistance test with a reading of 800K Ohms, this reading fluctuates between 800k Ohms and 1.2 M Ohms . The pass level is 1 M-Ohm, we are experiencing these readings on testing other main feed cables, so a programme of replacement is required.
Buyer
Medicines and Healthcare Products Regulatory Agency
Value
£600,000
Published
18 Nov 2016
Closes
6 May 2016
Procurement details
Source
Contracts Finder
Region
East of England
Procurement method
Other
Category
Works
Contract starts
Not provided
Contract ends
Not provided
CPV classifications
45310000
Electrical installation work
Lots
Lot default Main LV to Sub Main Feed Cable Replacement
£600,000
The existing cables are over 20 years old and have been subject to degradation due temperature variations through power loading and the local environment, currently the feed cable to FCS sub main panel failed an insulation resistance test with a reading of 800K Ohms, this reading fluctuates between 800k Ohms and 1.2 M Ohms . The pass level is 1 M-Ohm, we are...
Delivery: East of England · United Kingdom, East of England, United Kingdom
Documents
Unlock document linkOpportunity notice on Contracts Finder
23 Mar 2016
Opportunity notice on Contracts Finder
Tender notice · Web page
How to reply to a tender on our e-tendering portal - Bravo Solution.
Not provided
How to reply to a tender on our e-tendering portal - Bravo Solution.
Application/pdf · PDF
Contains public sector information licensed under the Open Government Licence v3.0.